Display information and fault information how to set bypass mode
It is worth sorting these as they usually don't improve when left
NOTE C02 is very useful and bypass can be selected depending on the model
Older models have a rocker switch under the battery cover labelled I/II this is the bypass control switch
Newer models need a button mash to get there hold 'ON' and 'SEL' for 4 seconds
At this point the UPS has stopped being a UPS but may still provide power on bypass
Control card is not inserted correctly
L02
L03
incorrect auxiliary power supply
L04
Heatsink over temperature
L05
Temperature sensor 1 fault
L07
Temperature sensor 2 fault
L10
Input fuse broken or input relay stuck (does not close)
L11
Input relay fault
L13
Capacitor pre-charge failed
L20
Capacitor bank undervoltage
L21
Capacitor bank overvoltage
L40
Inverter overvoltage
L41
Continuous output voltage
L42
Incorrect inverter voltage
L43
Inverter under voltage
L50
Overload - load > 103%
L51
Overload - load > 110%
L52
Overload - load > 150%
L53
Short circuit